Objects for presence detectors

Sensor function: with brightness sensor

Function

Name

Type

DPT

Flag

Presence detector - Switching

Sn Sensor channel - Output

1-bit

1,001

C, R, -, T, A

1-bit object for transmission of switching telegrams (ON, OFF).

This object is visible if the parameter "Function" is configured to "Switching".

Function

Name

Type

DPT

Flag

Presence detector - Brightness

Sn Sensor channel - Output

1-byte

5,001

C, R, -, T, A

1-byte object for sending brightness telegrams.

This object is visible if the "Function" parameter is parameterised to "Brightness value transmitter".

Function

Name

Type

DPT

Flag

Presence detector - scene number

Sn Sensor channel - Output

1-byte

17,001

C, R, -, T, A

1-byte object for sending scene telegrams.

This object is visible if the parameter "Function" is configured to "scene extension unit".

Function

Name

Type

DPT

Flag

Presence detector - Measured brightness value

Sn Sensor channel - Output

2-byte

9,004

C, R, -, T, A

2-byte object for sending the measured brightness.

Function

Name

Type

DPT

Flag

Presence detector - Disabling

Sn Sensor channel - Input

1-bit

1,003

C, -, W, -, U

1-bit object for activating or deactivating the disabling function. The object polarity can be configured.

Sensor function: without brightness sensor

Function

Name

Type

DPT

Flag

Presence detector - Switching

Sn Sensor channel - Output

1-bit

1,001

C, R, -, T, A

1-bit object for transmission of switching telegrams (ON, OFF).

This object is visible if the parameter "Function" is configured to "Switching".

Function

Name

Type

DPT

Flag

Presence detector - Brightness

Sn Sensor channel - Output

1-byte

5,001

C, R, -, T, A

1-byte object for sending brightness telegrams.

This object is visible if the "Function" parameter is parameterised to "Brightness value transmitter".

Function

Name

Type

DPT

Flag

Presence detector - scene number

Sn Sensor channel - Output

1-byte

17,001

C, R, -, T, A

1-byte object for sending scene telegrams.

This object is visible if the parameter "Function" is configured to "scene extension unit".

Function

Name

Type

DPT

Flag

Presence detector - Disabling

Sn Sensor channel - Input

1-bit

1,003

C, -, W, -, U

1-bit object for activating or deactivating the disabling function. The object polarity can be configured.