Parameters for presence detectors
DALI System... -> Configuration of sensor channels -> Sensor channel -> Sensor type: Presence detector
Sensor function: with brightness sensor
Function | No function Switching Brightness value transmitter Scene extension unit |
|---|---|
This parameter determines the function that is to be triggered when motion is detected. | |
Transmit at the beginning of a detection | Checkbox (yes / no) |
|---|---|
This parameter is used to trigger a switching command at the start of a detection. | |
Switching command | OFF ON |
|---|---|
This parameter defines the type of switching command at the start of a detection. This parameter is visible only if the function "Switching" is set. | |
Brightness value | 0 ... 100% |
|---|---|
This parameter defines the brightness value that is sent at the start of a detection. This parameter is only visible when the "Brightness value transmitter" function is set. | |
Scene number | 1 ... 64 |
|---|---|
This parameter is used to define the scene number that is sent at the start of a recording. This parameter is visible only if the function "Scene extension" is set. | |
Run-on time | 0 ... 59 min | 10 ... 30 ... 59 s |
|---|---|
This parameter specifies the time between the last motion detection and the end of detection. | |
Transmit at the end of a detection | Checkbox (yes / no) |
|---|---|
This parameter is used to set whether a switching command is still triggered at the end of detection. Depending on the set function, further parameters become visible. | |
Switching command | OFF ON |
|---|---|
This parameter defines the type of switching command at the end of a detection. This parameter is visible only if the function "Switching" is set. | |
Brightness value | 0 ... 100% |
|---|---|
This parameter defines the brightness value that is sent at the end of a detection. This parameter is only visible when the "Brightness value transmitter" function is set. | |
Scene number | 1, 2 ... 64 |
|---|---|
This parameter defines the scene number that is sent at the end of a recording. This parameter is visible only if the function "Scene extension" is set. | |
Brightness evaluation
The following parameters are not visible for the "without brightness sensor" sensor function.
Function | Brightness-dependent Brightness-independent |
|---|---|
This parameter determines whether the sensor should react to movements regardless of the ambient brightness or only if the brightness falls below a limit value. | |
Switch-on brightness | 10 ... 500 ... 2000 lux |
|---|---|
This parameter determines the brightness threshold below which motion detection triggers a switching operation. This parameter is only visible when the "Brightness-dependent" function is set. | |
Switch-off brightness (Hysteresis) | 10 ... 300 ... 800 lux |
|---|---|
This parameter is a hysteresis, i.e. a value that must be added to the switch-on brightness to arrive at the value of the switch-off brightness. If this value is exceeded, the "Run-on time after switch-off brightness" is started before the switch-off command is sent even if movement is detected. This parameter is only visible when the "Brightness-dependent" function is set. | |
Run-on time after switch-off brightness | 1 ... 5 ... 60 min |
|---|---|
If the switch-off threshold is exceeded, the switch-off command is not issued immediately, but the run-on time set in this parameter is started. The switch-off command is only sent after the time has elapsed. This parameter is only visible when the "Brightness-dependent" function is set. | |
Transmit brightness value | on change and cyclical on change cyclical |
|---|---|
This parameter defines when the measured brightness value is sent. | |
On change by | 5 ... 20 ... 200 lux |
|---|---|
If the brightness of the surroundings changes by the value set here, the brightness value is sent. This parameter is only visible if "Send brightness value" is set to "on change" or "on change and cyclically". | |
Cycle time | 0 ... 59 min | 10 ... 30 ... 59 s |
|---|---|
Cyclical sending is active. This parameter specifies the time interval at which the brightness values are sent. This parameter is only visible if "Send brightness value" is set to "cyclically" or "on change and cyclically". | |
Disabling function
Use disabling function | Checkbox (yes / no) |
|---|---|
At this point, the disabling function of the sensor channel can be activated. If this checkbox is activated, the ETS shows further communication object and parameters. | |
At the beginning of the disabling function | No reaction ON OFF |
|---|---|
When the disabling function is activated, the function configured here is triggered. Only applies to the "Switching" function of the sensor channel | |
At the beginning of the disabling function | no reaction Transmit value |
|---|---|
When the disabling function is activated, the function configured here is triggered. Only applies to the "Brightness value transmitter" function of the sensor channel | |
At the beginning of the disabling function | no reaction Send scene number |
|---|---|
When the disabling function is activated, the function configured here is triggered. Only applies to the "scene extension unit" function of the sensor channel | |
At the end of the disabling function | No reaction as for beginning of a detection as for end of a detection Track status as before the lockdown |
|---|---|
When disabling is cancelled, the function configured here is triggered. | |
Object polarity | 0 = enable / 1 = disable 1 = enable / 0 = disable |
|---|---|
This parameter defines the value of the disabling object at which the disabling function is active. | |