Parameters for push-buttons
DALI System... -> Configuration sensor channels -> Sensor channel -> Sensor type: Push-button
Sensor function: Switching
When pressed | No reaction ON OFF TOGGLE |
|---|---|
This parameter defines the reaction when the push-button is pressed. | |
When released | No reaction ON OFF TOGGLE |
|---|---|
This parameter determines the reaction when the push-button is released. | |
Use disabling function | Checkbox (yes / no) |
|---|---|
At this point, the disabling function of the sensor channel can be activated. If this checkbox is activated, the ETS shows further communication object and parameters. | |
At the beginning of the disabling function | No reaction ON OFF TOGGLE |
|---|---|
When the disabling function is activated, the function configured here is triggered. | |
At the end of the disabling function | No reaction transmit current state ON OFF TOGGLE |
|---|---|
When disabling is cancelled, the function configured here is triggered. | |
Object polarity | 0 = enable / 1 = disable 1 = enable / 0 = disable |
|---|---|
This parameter defines the value of the disabling object at which the disabling function is active. | |
Sensor function: Dimming

Brightness on pressing | No reaction Brighter (ON) Darker (OFF) Brighter/darker (TOGGLE) Brighter (TOGGLE) Darker (TOGGLE) |
|---|---|
This parameter defines the reaction when the push-button is pressed. | |
Extended settings | Checkbox (yes / no) |
|---|---|
When the advanced parameters are activated, the ETS shows the following parameters. | |
Time between switching and dimming | 0 ... 50 s | 200 ... 400 ... 990 ms |
|---|---|
This parameter defines how long the button must be pressed for a dimming telegram to be transmitted. | |
Dimming brightness by | 1.5 % 3 % 6 % 12.5 % 25 % 50 % 100 % |
|---|---|
This parameter sets the relative dimming level when the brightness is increased. On each button actuation, the brightness is changed at maximum by the configured step width. | |
Dimming darker by | 1.5 % 3 % 6 % 12.5 % 25 % 50 % 100 % |
|---|---|
This parameter sets the relative dimming level when the brightness is reduced. On each button actuation, the brightness is changed at maximum by the configured step width. | |
Stop telegram | Checkbox (yes / no) |
|---|---|
If the checkbox is activated, the device transmits a telegram for stopping the dimming process when the button is released. When the device transmits telegrams for dimming in smaller levels, the stop telegram is generally not needed. | |
Telegram repetition | Checkbox (yes / no) |
|---|---|
This parameter can be used to activate telegram repetition for dimming. With telegram repetition activated, the device cyclically sends relative dimming telegrams (in the parameterised step width) to the bus if the button is pressed long. | |
Time between two telegrams | 200 ms 300 ms 400 ms 500 ms 750 ms 1000 ms 2000 ms |
|---|---|
This parameter defines the interval at which the dimming telegrams are automatically repeated in the telegram repetition mode. | |
Use disabling function | Checkbox (yes / no) |
|---|---|
At this point, the disabling function of the sensor channel can be activated. If this checkbox is activated, the ETS shows further communication object and parameters. | |
At the beginning of the disabling function | No reaction ON OFF TOGGLE |
|---|---|
When the disabling function is activated, the function configured here is triggered. | |
At the end of the disabling function | no reaction transmit current state ON OFF TOGGLE |
|---|---|
When disabling is cancelled, the function configured here is triggered. | |
Object polarity | 0 = enable / 1 = disable 1 = enable / 0 = disable |
|---|---|
This parameter defines the value of the disabling object at which the disabling function is active. | |
Sensor function: Venetian blind / shutter / awning / roof window
Type of blind/shutter | Venetian blind Shutter / awning / roof window |
|---|---|
This parameter defines the type of blind/shutter to be controlled and optimises the available setting options of the channel function. | |
Command on pressing | UP DOWN TOGGLE |
|---|---|
This parameter defines the running direction of the drive on pressing the push-button. If the setting is "TOGGLE", the direction is changed after each long time command. If several devices are to control the same drive, the long-time objects of the devices must be interlinked to ensure that the running direction can be changed correctly. | |
Command sequence | Up/down - Step Step - Up/down |
|---|---|
Two different operating concepts can be selected to actuate the "shutter / awning / roof window" blind/shutter types. | |
Command sequence | Step - Up/down - Step Up/down - Step Step - Up/down Step - Up/down or step |
|---|---|
For Venetian blind control, four different operating concepts can be selected. | |
Long button actuation from (t1) | 0 ... 59 s | 200 ... 400 ... 990 ms |
|---|---|
This parameter sets the time after which the long-time operation will be evaluated on pressing the button. This parameter is not visible for the "command sequence = Up/down - Step" | |
Time window for slat adjustment (t2) | 0 ... 59 s | 200 ... 500 ... 990 ms |
|---|---|
The time during which a transmitted MOVE telegram can be terminated by releasing the button (STEP) is set here. This function serves to adjust the slats of a venetian blind. This parameter is only visible for "Type of blind/shutter = Venetian blind", but not for "command sequence = Up/down - Step". | |
Show info graphic | Active Inactive |
|---|---|
With activated info graphic, the graphic diagram of the command sequence and related text information are displayed. | |
Use disabling function | Checkbox (yes / no) |
|---|---|
At this point, the disabling function of the sensor channel can be activated. If this checkbox is activated, the ETS shows further communication object and parameters. | |
At the beginning of the disabling function | no reaction UP DOWN |
|---|---|
When the disabling function is activated, the function configured here is triggered. | |
At the end of the disabling function | no reaction transmit current state UP DOWN |
|---|---|
When disabling is cancelled, the function configured here is triggered. | |
Object polarity | 0 = enable / 1 = disable 1 = enable / 0 = disable |
|---|---|
This parameter defines the value of the disabling object at which the disabling function is active. | |
Sensor function: Value transmitter
Data point type | Value range | DPT 5.001 | 0 ... 100% DPT 5.010 | 0 ... 255 DPT 5.003 | 0 ... 360° DPT 5.004 | 0 ... 255% DPT 6.010 | -128 ... 127 DPT 7.001 | 0 ... 65535 DPT 7.600 | 1000 ... 10000 K DPT 8.001 | -32768 ... 32767 DPT 9.001 | 0 ... 40 °C DPT 9.004 | 0 ... 1500 lux DPT 249.600 | Colour temperature value + brightness RGB/HSV (RGB: DPT 232.600, HSV: DPT 5.003, DPT 5.001, DPT 5.001) RGBW/HSVW (RGBW: DPT 251.600, HSVW: DPT 5.003, DPT 5.001, DPT 5.001, DPT 5.001) |
|---|---|
The "value transmitter" function distinguishes between 1-byte, 2-byte 3-byte and 6-byte values. The following parameters and their settings depend on the setting for this parameter. | |
Value when pressed | 0 ... 100% |
|---|---|
This parameter defines the object value when the push-button is pressed. It is visible only if "data point type | value range = DPT 5.001 | 0 ... 100%". | |
Value when pressed | 0 ... 255 |
|---|---|
This parameter defines the object value when the push-button is pressed. It is visible only if "data point type | value range = DPT 5.010 | 0 ... 255". | |
Value when pressed | 0 ... 360° |
|---|---|
This parameter defines the object value when the push-button is pressed. It is visible only if "data point type | value range = DPT 5.003 | 0 ... 360°". | |
Value when pressed | 0 ... 255% |
|---|---|
This parameter defines the object value when the push-button is pressed. It is visible only if "data point type | value range = DPT 5.004 | 0 ... 255%". | |
Value when pressed | -128...0 ...127 |
|---|---|
This parameter defines the object value when the push-button is pressed. It is visible only if "data point type | value range = DPT 6.010 | -128 ... 127". | |
Value when pressed | 0 ... 65535 |
|---|---|
This parameter defines the object value when the push-button is pressed. It is visible only if "data point type | value range = DPT 7.001 | 0 ... 65535". | |
Color temperature value when pressed
| 1000 ... 2700 ... 10000 K |
|---|---|
This parameter defines the object value when the push-button is pressed. It is visible only if "data point type | value range = DPT 7.600 | 1000 ... 10000 K". | |
Value when pressed | -32768 ... 0 ... 32767 |
|---|---|
This parameter defines the object value when the push-button is pressed. It is visible only if "data point type | value range = DPT 8.001 | -32768 ... 32767". | |
Temperature value when pressed | 0 ... 20 ... 40 °C |
|---|---|
This parameter defines the object value when the push-button is pressed. It is visible only if "data point type | value range = DPT 9.001 | 0 ... 40 °C". | |
Brightness value when pressed | 0, 50 ... 300 ... 1500 lux |
|---|---|
This parameter defines the object value when the push-button is pressed. It is visible only if "data point type | value range = DPT 9.004 | 0 ... 1500 lux". | |
Color temperature value when pressed | 1000 ... 2700 ... 10000 K |
|---|---|
This parameter defines the object value when the push-button is pressed. It is visible only if "data point type | value range = DPT 249.600 | colour temperature value + brightness". | |
Brightness value when pressed | 0 ... 100% |
|---|---|
This parameter defines the object value when the push-button is pressed. It is visible only if "data point type | value range = DPT 249.600 | colour temperature value + brightness". | |
Adjustment duration in the actuator | 0 ... 100 min, 0, 1 ... 59 s, 0 ... 900 ms |
|---|---|
This parameter defines the object value when the push-button is pressed. It is visible only if "data point type | value range = DPT 249.600 | colour temperature value + brightness". | |
Color value when pressed | #000000 ... #FFFFFF |
|---|---|
This parameter determines the object values of the value transmitter 3-byte (or value transmitter 6-byte), brightness value (V), saturation (S) and colour hue (H) objects when the push-button is pressed. It is visible for "Data point type | value range = RGB/HSV (RGB: DPT 232.600, HSV: DPT 5.003, DPT 5.001, DPT 5.001)", "Data point type | value range = RGB/HSV (RGB: DPT 232.600, HSV: DPT 5.003, DPT 5.001, DPT 5.001)" and "Data point type | value range = RGBW/HSVW (RGBW: DPT 251.600, HSVW: DPT 5.003, DPT 5.001, DPT 5.001, DPT 5.001)". The value (RGB/HSV) is configured by means of a colour picker. With the data point type | value range "RGBW/HSVW (RGBW: DPT 251.600, HSVW: DPT 5.003, DPT 5.001, DPT 5.001, DPT 5.001)", the white value is configured by means of a separate slider. | |
White value | 0 ... 255 |
|---|---|
This parameter defines the object value white level (W) when the push-button is pressed. It is visible only if "data point type | value range = RGBW/HSVW (RGBW: DPT 251.600, HSVW: DPT 5.003, DPT 5.001, DPT 5.001, DPT 5.001)". | |
Use disabling function | Checkbox (yes / no) |
|---|---|
At this point, the disabling function of the sensor channel can be activated. If this checkbox is activated, the ETS shows further communication object and parameters. | |
At the beginning of the disabling function | No reaction Transmit value |
|---|---|
When the disabling function is activated, the function configured here is triggered. | |
Value | 0 ... 100% |
|---|---|
This parameter determines the object value at the beginning of the disabling. It is visible only if "data point type | value range = DPT 5.001 | 0 ... 100%". | |
Value | 0 ... 255 |
|---|---|
This parameter determines the object value at the beginning of the disabling. It is visible only if "data point type | value range = DPT 5.010 | 0 ... 255". | |
Value | 0 ... 360° |
|---|---|
This parameter determines the object value at the beginning of the disabling. It is visible only if "data point type | value range = DPT 5.003 | 0 ... 360°". | |
Value | 0 ... 255% |
|---|---|
This parameter determines the object value at the beginning of the disabling. It is visible only if "data point type | value range = DPT 5.004 | 0 ... 255%". | |
Value | -128...0 ...127 |
|---|---|
This parameter determines the object value at the beginning of the disabling. It is visible only if "data point type | value range = DPT 6.010 | -128 ... 127". | |
Value | 0 ... 65535 |
|---|---|
This parameter determines the object value at the beginning of the disabling. It is visible only if "data point type | value range = DPT 7.001 | 0 ... 65535". | |
Color temperature value
| 1000 ... 2700 ... 10000 K |
|---|---|
This parameter determines the object value at the beginning of the disabling. It is visible only if "data point type | value range = DPT 7.600 | 1000 ... 10000 K". | |
Value | -32768 ... 0 ... 32767 |
|---|---|
This parameter determines the object value at the beginning of the disabling. It is visible only if "data point type | value range = DPT 8.001 | -32768 ... 32767". | |
Temperature value | 0 ... 20 ... 40 °C |
|---|---|
This parameter determines the object value at the beginning of the disabling. It is visible only if "data point type | value range = DPT 9.001 | 0 ... 40 °C". | |
Brightness value | 0, 50 ... 300 ... 1500 lux |
|---|---|
This parameter determines the object value at the beginning of the disabling. It is visible only if "data point type | value range = DPT 9.004 | 0 ... 1500 lux". | |
Color temperature value | 1000 ... 2700 ... 10000 K |
|---|---|
This parameter determines the object value at the beginning of the disabling. It is visible only if "data point type | value range = DPT 249.600 | colour temperature value + brightness". | |
Brightness value | 0 ... 100% |
|---|---|
This parameter determines the object value at the beginning of the disabling. It is visible only if "data point type | value range = DPT 249.600 | colour temperature value + brightness". | |
Adjustment duration in the actuator | 0 ... 100 min, 0, 1 ... 59 s, 0 ... 900 ms |
|---|---|
This parameter determines the object value at the beginning of the disabling. It is visible only if "data point type | value range = DPT 249.600 | colour temperature value + brightness". | |
Color value | #000000 ... #FFFFFF |
|---|---|
This parameter determines the object values of the 3-byte value transmitter (or 6-byte value transmitter), brightness value (V), saturation (S) and colour hue (H) objects at the beginning of the disabling. It is visible for "Data point type | value range = RGB/HSV (RGB: DPT 232.600, HSV: DPT 5.003, DPT 5.001, DPT 5.001)" and "Data point type | value range = RGBW/HSVW (RGBW: DPT 251.600, HSVW: DPT 5.003, DPT 5.001, DPT 5.001, DPT 5.001)". The value (RGB/HSV) is configured by means of a colour picker. With the data point type | value range "RGBW/HSVW (RGBW: DPT 251.600, HSVW: DPT 5.003, DPT 5.001, DPT 5.001, DPT 5.001)", the white value is configured by means of a separate slider. | |
White value | 0 ... 255 |
|---|---|
This parameter determines the object value of the white value (W) object at the beginning of the disabling. It is visible only if "data point type | value range = RGBW/HSVW (RGBW: DPT 251.600, HSVW: DPT 5.003, DPT 5.001, DPT 5.001, DPT 5.001)". | |
At the end of the disabling function | no reaction transmit current state Transmit value |
|---|---|
In addition to disabling the channel, the device can trigger the function configured here when disabling is lifted. Immediately react at the end of the disabling. This parameter defines the reaction of the channel at the end of the disabling. | |
Value | 0 ... 100% |
|---|---|
This parameter determines the object value at the end of the disabling. It is visible only if "data point type | value range = DPT 5.001 | 0 ... 100%". | |
Value | 0 ... 255 |
|---|---|
This parameter determines the object value at the end of the disabling. It is visible only if "data point type | value range = DPT 5.010 | 0 ... 255". | |
Value | 0 ... 360° |
|---|---|
This parameter determines the object value at the end of the disabling. It is visible only if "data point type | value range = DPT 5.003 | 0 ... 360°". | |
Value | 0 ... 255% |
|---|---|
This parameter determines the object value at the end of the disabling. It is visible only if "data point type | value range = DPT 5.004 | 0 ... 255%". | |
Value | -128...0 ...127 |
|---|---|
This parameter determines the object value at the end of the disabling. It is visible only if "data point type | value range = DPT 6.010 | -128 ... 127". | |
Value | 0 ... 65535 |
|---|---|
This parameter determines the object value at the end of the disabling. It is visible only if "data point type | value range = DPT 7.001 | 0 ... 65535". | |
Color temperature value
| 1000 ... 2700 ... 10000 K |
|---|---|
This parameter determines the object value at the end of the disabling. It is visible only if "data point type | value range = DPT 7.600 | 1000 ... 10000 K". | |
Value | -32768 ... 0 ... 32767 |
|---|---|
This parameter determines the object value at the end of the disabling. It is visible only if "data point type | value range = DPT 8.001 | -32768 ... 32767". | |
Temperature value | 0 ... 20 ... 40 °C |
|---|---|
This parameter determines the object value at the end of the disabling. It is visible only if "data point type | value range = DPT 9.001 | 0 ... 40 °C". | |
Brightness value | 0, 50 ... 300 ... 1500 lux |
|---|---|
This parameter determines the object value at the end of the disabling. It is visible only if "data point type | value range = DPT 9.004 | 0 ... 1500 lux". | |
Color temperature value | 1000 ... 2700 ... 10000 K |
|---|---|
This parameter determines the object value at the end of the disabling. It is visible only if "data point type | value range = DPT 249.600 | colour temperature value + brightness". | |
Brightness value | 0 ... 100% |
|---|---|
This parameter determines the object value at the end of the disabling. It is visible only if "data point type | value range = DPT 249.600 | colour temperature value + brightness". | |
Adjustment duration in the actuator | 0 ... 100 min, 0, 1 ... 59 s, 0 ... 900 ms |
|---|---|
This parameter determines the object value at the end of the disabling. It is visible only if "data point type | value range = DPT 249.600 | colour temperature value + brightness". | |
Color value | #000000 ... #FFFFFF |
|---|---|
This parameter determines the object values of the 3-byte value transmitter (or 6-byte value transmitter), brightness value (V), saturation (S) and colour hue (H) objects at the end of the disabling. It is visible for "Data point type | value range = RGB/HSV (RGB: DPT 232.600, HSV: DPT 5.003, DPT 5.001, DPT 5.001)" and "Data point type | value range = RGBW/HSVW (RGBW: DPT 251.600, HSVW: DPT 5.003, DPT 5.001, DPT 5.001, DPT 5.001)". The value (RGB/HSV) is configured by means of a colour picker. With the data point type | value range "RGBW/HSVW (RGBW: DPT 251.600, HSVW: DPT 5.003, DPT 5.001, DPT 5.001, DPT 5.001)", the white value is configured by means of a separate slider. | |
White value | 0 ... 255 |
|---|---|
This parameter determines the object value of the white value (W) object at the end of the disabling. It is visible only if "data point type | value range = RGBW/HSVW (RGBW: DPT 251.600, HSVW: DPT 5.003, DPT 5.001, DPT 5.001, DPT 5.001)". | |
Object polarity | 0 = enable / 1 = disable 1 = enable / 0 = disable |
|---|---|
This parameter defines the value of the disabling object at which the disabling function is active. | |
Sensor function: Scene extension
Short button operation | Recall scene Switch over scene |
|---|---|
This parameter defines the functionality of the scene extension unit. If the device is used as a scene extension unit, the scenes can either be stored in one or several other KNX devices (e. g. light scene push button sensor). When a scene is recalled, the device transmits a telegram with the respective scene number via the extension object of the button. | |
Scene number | 1...64 |
|---|---|
In accordance with the KNX standard, objects with data type 18.001 "Scene Control" can retrieve or store up to 64 scenes by their numbers. The parameter defines the scene number to be transmitted when the button is pressed. | |
First scene number | 1...64 |
|---|---|
In accordance with the KNX standard, objects with data type 18.001 "Scene Control" can retrieve or store up to 64 scenes by their numbers. The parameter defines the scene number to be transmitted when the button is pressed. The input of the first scene number is available only if "Switch over scene" is active in the event of the "short button actuation" command. | |
Second scene number | 1, 2 ... 64 |
|---|---|
In accordance with the KNX standard, objects with data type 18.001 "Scene Control" can retrieve or store up to 64 scenes by their numbers. The parameter defines the scene number to be transmitted when the button is pressed. The input of the second scene number is available only if "Switch over scene" is active in the event of the "short button actuation" command. | |
Long button operation | No reaction Memory function |
|---|---|
This parameter defines the functionality of the scene extension unit. If the device is used as a scene extension unit, the scenes can either be stored in one or several other KNX devices (e. g. light scene push button sensor). With activated storage function, the device transmits a telegram with the respective scene number via the extension object of the button. | |
Use disabling function | Checkbox (yes / no) |
|---|---|
At this point, the disabling function of the sensor channel can be activated. If this checkbox is activated, the ETS shows further communication object and parameters. | |
At the beginning of the disabling function | no reaction Recall scene |
|---|---|
When the disabling function is activated, the function configured here is triggered. | |
At the end of the disabling function | no reaction transmit current state Recall scene |
|---|---|
When disabling is cancelled, the function configured here is triggered. | |
Object polarity | 0 = enable / 1 = disable 1 = enable / 0 = disable |
|---|---|
This parameter defines the value of the disabling object at which the disabling function is active. | |