Value transmitter
The "value transmitter" sensor function can be configured for the "push-button" sensor type. The ETS indicates up to six communication objects for the "value transmitter" function. The parameters can be used to determine the value the "value transmitter" objects obtain when the button is pressed.
With the "value transmitter" function, the device sends parameterised values to the bus at the press of a button.
A disabling function can also be activated. No distinction is made between a brief or long press.
Value ranges
The value transmitter knows 13 different value ranges. The parameter "Data point type | Value range" determines the value range used by the value transmitter, depending on the application case:
Function | Function | Lower numerical limit | Upper numerical limit |
|---|---|---|---|
1-byte value transmitter | 0...100% | 0% | 100% |
1-byte value transmitter | 0...255 | 0 | 255 |
1-byte value transmitter | 0…360° | 0° | 360° |
1-byte value transmitter | 0...255% | 0% | 255% |
1-byte value transmitter | -128...127 | -128 | 127 |
2-byte value transmitter | 0...65535 | 0 | 65535 |
2-byte value transmitter | Color temperature value | 1000 K | 10000 K |
2-byte value transmitter | -32768...32767 | -32768 | 32767 |
2-byte value transmitter | Temperature value | 0 °C | 40 °C |
2-byte value transmitter | Brightness value | 0 lux | 1500 lux |
6-byte value transmitter | Colour temperature value + brightness | 1000 K | 0% | 10000 K | 100% |
3-byte value transmitter | RGB/HSV | #000000 | #FFFFFF |
6-byte value transmitter | RGBW/HSVW | #000000 + 0 | #FFFFFF + 255 |
For each of these ranges, the value that can be transmitted to the bus for each button actuation is configurable.