Objects for scenes
Function | Name | Type | DPT | Flag |
|---|---|---|---|---|
Scenes - Extension unit | DALI System... - Input | 1-byte | 18,001 | C, -, W, -, U |
1-byte object for recalling scenes (bit 7 deleted) or for storing new scene values (bit 7 set). Bits 0...6 carry the KNX scene number (data value 0...63 -> KNX scene number 1...64). | ||||
Function | Name | Type | DPT | Flag |
|---|---|---|---|---|
Extended scene recall | DALI System... - Input | 1-bit | 1,001 | C, -, W, -, U |
1-bit object for extended scene recall. Each ON telegram received recalls the next scene in sequence. Each OFF telegram received recalls the previous scene. After a reset (bus/mains voltage return, ETS programming operation), an ON or OFF telegram always recalls scene 1 first. | ||||