Objects for scenes

Function

Name

Type

DPT

Flag

Scenes - Extension unit

DALI System... - Input

1-byte

18,001

C, -, W, -, U

1-byte object for recalling scenes (bit 7 deleted) or for storing new scene values (bit 7 set). Bits 0...6 carry the KNX scene number (data value 0...63 -> KNX scene number 1...64).

Function

Name

Type

DPT

Flag

Extended scene recall

DALI System... - Input

1-bit

1,001

C, -, W, -, U

1-bit object for extended scene recall. Each ON telegram received recalls the next scene in sequence. Each OFF telegram received recalls the previous scene. After a reset (bus/mains voltage return, ETS programming operation), an ON or OFF telegram always recalls scene 1 first.