Objects for Colour Transition Mode (CTM)

Function

Name

Type

DPT

Flag

Daytime colour sequence (CTM) - Start/stop

Group 1...32 / Single device 1...64

1-bit

1,003

C, -, W, -, U

1-bit object for starting and stopping a daytime colour sequence ("1" = start, "0" = stop).

After the start, the execution of the daytime colour sequence begins according to the current time and day of the week. When stopped, the execution of the daytime colour sequence is immediately stopped.

 

Function

Name

Type

DPT

Flag

Daytime colour sequence (CTM) - Switch matrix

Group 1...32 / Single device 1...64

1-byte

17,001

C, -, W, -, U

1-byte object for switching the effective CTM matrix (1...4) during operation of the gateway.

In principle, it is only possible to switch to the four CTM matrices configured in the ETS. There is no reaction if a matrix number (5...64) is received by means of the switch-over object not included in the configuration of the matrices.

After an ETS programming operation or the mains voltage returns, the last switchover by means of the object is lost (object value "0"). A new telegram must first be received so that a new switchover becomes active.

 

Function

Name

Type

DPT

Flag

Daytime colour sequence (CTM) - Status

Group 1...32 / Single device 1...64

1-bit

1,003

C, R, -, T, A

1-bit object for displaying the status of the active day colour gradient (CTM). ("1" = day colour gradient active, "0" = day colour gradient not active)

 

Function

Name

Type

DPT

Flag

Daytime colour sequence (CTM) - Active matrix

Group 1...32 / Single device 1...64

1-byte

17,001

C, R, -, T, A

1-byte object for displaying the status of the active CTM matrix (1...4) during gateway operation.