Object list for operation and indication
Manual control
Function | Name | Type | DPT | Flag |
|---|---|---|---|---|
Locking | Manual operation - Input | 1-bit | 1,003 | C, (R), W, -, A |
1-bit object for disabling the manual operation on the device. The polarity can be configured. | ||||
Function | Name | Type | DPT | Flag |
|---|---|---|---|---|
Status | Manual operation - Output | 1-bit | 1,002 | C, R, -, T, A |
1-bit object for transmission of the manual operation status. The object is "OFF" when manual operation is deactivated (bus control). The object is "ON" when manual operation is activated. You can configure whether temporary or permanent manual operation will be indicated as status information or not. | ||||
Function | Name | Type | DPT | Flag |
|---|---|---|---|---|
Temporary status indication | Manual operation - Input/Output | 1-bit | 1,017 | C, (R), W, T, A |
1-bit object to signal and activate the temporary status indication. This object is bidirectional and can firstly signal the status of the temporary status indication, and secondly, activate the status display. If a temporary status indication has been activated by pressing the "Manual operation" button, the object transmits the value "ON". The object is visible only if the temporary status indication is activated with control by means of the object. | ||||
Broadcast control
Function | Name | Type | DPT | Flag |
|---|---|---|---|---|
Switching | DALI system .. – Broadcast control - Input | 1-bit | 1,001 | C, -, W, -, U |
1-bit object for switching all DALI operating devices connected to the DALI system. | ||||
Function | Name | Type | DPT | Flag |
|---|---|---|---|---|
Dimming | DALI system .. – Broadcast control - Input | 4-bit | 3,007 | C, -, W, -, U |
4-bit object for dimming all DALI operating devices connected to the DALI system. | ||||
Function | Name | Type | DPT | Flag |
|---|---|---|---|---|
Brightness value | DALI system .. – Broadcast control - Input | 1-byte | 5,001 | C, -, W, -, U |
1-byte object for calling up the brightness value of all DALI operating devices connected to the DALI system. | ||||