Parameters for DALI communication

DALI System... -> General

DALI telegram rate limit

Checkbox (yes / no)

Optionally, to reduce the telegram load for the DALI operating devices, and thus reduce the likelihood of errors on the part of some electronic ballasts, it is possible to increase the pause time between commands of the DALI gateway to the operation device. This results in a telegram rate limitation, which can be enabled at this point. Further parameters become available when the function is enabled.

 

Minimum time delay between two DALI commands

14 ms

20 ms

27 ms

34 ms

41 ms

47 ms

54 ms

61 ms

68 ms

If telegram rate limitation is activated, this parameter defines the delay between the DALI commands of the gateway.

 

Delay after voltage return

1...10...30 s

After the mains voltage supply is switched on, DALI operating devices usually require different lengths of time to initialise themselves and thus to react to commands of the gateway, depending on their type. To ensure that, after the mains voltage returns, no commands of the gateway to the operating devices are lost, because they are still initialising, it is possible to configure a delay as an option here.

This parameter can be activated only if telegram rate limitation is activated.