Technical data

KNX

 

KNX medium

TP 256

KNX commissioning mode

S mode

Rated voltage KNX

DC 21 ... 32 V SELV

Current consumption KNX

4.5 ... 5.0 mA

Connection type for bus

Device connection terminal

 

 

Supply

 

Rated voltage

AC 110 ... 240 V ~

Mains frequency

50 / 60 Hz

Rated voltage

DC 110 ... 240 V

Power loss

Max. 3 W

 

 

DALI

 

Rated voltage DALI

DC 16 V (typ.)

Output current per DALI system

Typ. 128 mA, max. 250 mA for short periods

Guaranteed bus current per DALI system

148 mA

The DALI systems are supplied with power exclusively via the DALI Gateway. The connection of an additional power supply to one of the DALI systems is not permitted.

Addressable DALI operating devices

max. of 64 per DALI system

Addressable DALI sensors

max. of 32 per DALI system

The number of DALI operating devices and DALI sensors must be designed so that the total current consumption of 148mA per DALI system is not exceeded.

DALI transmission rate

1.2 kBit/s

DALI protocol

EN 62386

Duration of the starting operation

Max. 20 s

Cable type

Sheathed cable 230 V, e. g. NYM

DALI cable length

(DALI cable length)

DALI cable length

Ambient conditions

 

Ambient temperature

-5 ... +45 °C

Storage temperature

-5 ... +45 °C

Transport temperature

-25 ... +70 °C

Clampable cable cross-sections

(Clampable cable cross-sections)

Clampable cable cross-sections

Installation width

72 mm / 4 HP

 

 

Terminals

 

Connection mode

Screw terminal

Stripping length

8 mm

Suitable tool

 

 

Phillips screwdriver (recommended)

PZ1 Plusminus (Pozidriv/slotted)

 

 

Phillips screwdriver

PZ1

 

 

Slotted screwdriver

4 mm

 

Connection torque

max. 0.8 Nm