Device components

(1) |
|
(2) | LED |
(3) |
|
(4) | LED |
(5) |
|
(6) | LED |
(7) | Button – Switch off all DALI devices |
(8) | Seven-segment display for indication of the number (1...16, 1...32) of a DALI group (8a) or the short address (1...64) of a single device (8b) selected by manual operation. In bus mode, there is no indication of the group number or short address. In addition, to indicator additional information: bc: indication during manual operation in broadcast mode (unprogrammed state, central control). Er: indication of an impermissible external voltage at the DALI device connection terminals (e.g. mains voltage connected). DALI gateway without function. The device is ready for operation again as soon as there is no longer an error. db: a high telegram load has been detected in the DALI system signalled by the LED (9). This high load can lead to disturbed operation (noticeable delays, telegram loss). LE: signals automatic device replacement. E: signals an error during automatic device replacement. |
(9) | LED of the active DALI system lights up in manual operation or after pressing the change-over button (only with "2fold" device variant) |
(10) | Change-over button for DALI systems 1 and 2 (only with "2fold" device variant) |
(11) | KNX connection |
(12) | Programming button and LED |
(13) | Device connection terminals for DALI systems 1 & 2 (number depends on the device variant) |
(14) | Terminals for mains supply |
button – Manual control
button – Switch on or increase brightness
button – Switch off or reduce brightness